Home > Eaton / Cutler Hammer >

XTOBP60CC1

Eaton XTOBP60CC1 overload relay

 
Alternative Views:


Eaton XTOBP60CC1 thermal overload relay that is adjustable from 0.40 to 0.60 AMPS and has manual/automatic reset options. This 3 pole Eaton overload mounts directly to the XTCE018C10, XTCE025C10 and XTCE032C10 contactors and is used for Class 10 (trips in 10 seconds or less in over current situations) motor protection. A set of auxiliary contacts, one N.O. and one N.C., are included on the XTOBP60CC1 and used for cutting power to the coil when the overload trips.

Need a slightly lower AMP range? Click here to see the XTOBP40CC1.
Need a slightly higher AMP range? Click here to see the XTOB001CC1.

XTOBP60CC1 Datasheet

List Price: $140.56
Our Price: $47.94
Savings: $92.62

Quantity in Stock:(Out of Stock)

Availability : Out of Stock - Can ship in 1-2 weeks
Product Code: XTOBP60CC1


Eaton XTOB Mounting Brackets:
Check here if you need a separate mounting bracket for attaching this XTOM overload to DIN rail [Add $9.17]

Qty:  
Description Detailed Specifications Shipping and Warranty Information
 
The XTOB overload relays by Eaton provide a consistent, reliable and economical solution to your motor-protection needs. All XTOB relays are directly mounted to the XTCE contactors, minimizing spacing and installation time. Each overload relay has both a manual and automatic trip and reset button to suit your specific system. Also each XTOB relay is certified as Class 10 protection, which means it will trip within 10 seconds of a locked motor condition, saving you the time and expense of replacing your motor.

Adding this Eaton overload relay is essential to provide full circuit protection of your motor. Simply using a contactor will not provide the necessary level of protection that an overload can and will cause severe damage to your motor should a high load situation occur. With phase loss protection and an easy-to-use dial on the front of the XTOB, these overload relays are simple to set and adjust to your specific AMP needs. Also with a built in auxiliary contact for trip indication, you can trigger any other electrical equipment of this overload condition thus saving other failures and damages to your system.
Technical Specifications
  • Class 10 overload; trip response from 2 to 10 seconds
  • Ambient compensated, bimetallic overload tripping mechanism
  • Phase failure sensitive to IEC/EN 60947
  • Manual / Automatic reset button
  • Built-in NO and NC auxiliary contacts