Schneider Electric (formerly Square D and Telemecanique) has introduced a new style to the low voltage D-line contactors. These 40-65 AMP contactors have the narrowest profile of any contactor this size in the industry. These new LC1D65AD7 slim line contactors are only 2.17 inches wide, as compared to the standard 3 inches wide of normal contactors for this AMP size. This lowers cost by reducing panel size for both small starters as well for your complex UL panel application.
The LC1D65AD7 has a 42 volt AC coil, is rated for 65 AMPS and has UL, CSA, IEC and CE approvals for use in a wide variety of applications. This 65 AMP contactor has finger safe terminals for protection to IP 2X and has a coil tolerance of +10% to -15% to suit all of your electrical needs.
MAXIMUM HORSEPOWER | MAXIMUM CURRENT | # OF POLES | AUXILIARY CONTACTS | CATALOG # | COIL VOLTAGE | Single Phase | Three Phase | Inductive AC-1 (A) | Resistive AC-3 (A) | N.O. | N.C. | N.O. | N.C. | 115v HP | 230v HP | 200v HP | 230v HP | 460v HP | 575v HP | 5 | 10 | 20 | 20 | 40 | 50 | 65 | 80 | 3 | 0 | 1 | 1 | LC1D65AD7 | 42v50/60Hz |
Rated insulation voltage (Vi) : 690v UL/CSA
Rated impulse withstand voltage (Vimp) : 8kV
Conforming to standards : IEC 60947-1, 60947-4-1, VDE 0660, EN 60947-1, EN 60947-4-1.
Degree of protection : Protection against direct finger contact IP 2X
Ambient air temperature around the device : - 5 to + 55 °C (+23 to +131 °F)
Rated operational voltage (Ve) : 1000V
Control voltage limits : 0.85 to 1.1 Vac at 60 Hz
Average consumption at 20 °C (68 °F) and at Vc : 220VA
Mechanical durability of operating cycles : 16,000,000
Mechanical life at Uc : 30,000,000
|