Schneider Electric (formerly Square D and Telemecanique) has introduced a new style to the low voltage D-line contactors. These 40-65 AMP contactors have the narrowest profile of any contactor this size in the industry. These new LC1D slim line contactors are only 2.17 inches wide, as compared to the standard 3 inches wide of normal contactors for this AMP size. This lowers cost by reducing panel size for both small starters as well for your complex UL panel application.
MAXIMUM HORSEPOWER | MAXIMUM CURRENT | # OF POLES | AUXILIARY CONTACTS | CATALOG # | COIL VOLTAGE | Single Phase | Three Phase | Inductive AC-1 (A) | Resistive AC-3 (A) | N.O. | N.C. | N.O. | N.C. | 115v HP | 230v HP | 200v HP | 230v HP | 460v HP | 575v HP | 3 | 7.5 | 15 | 15 | 40 | 40 | 50 | 80 | 3 | 0 | 1 | 1 | LC1D50A | |
Rated insulation voltage (Vi) : 690v UL/CSA
Rated impulse withstand voltage (Vimp) : 8kV
Conforming to standards : IEC 60947-1, 60947-4-1, VDE 0660, EN 60947-1, EN 60947-4-1.
Degree of protection : Protection against direct finger contact IP 2X
Ambient air temperature around the device : - 5 to + 55 °C (+23 to +131 °F)
Rated operational voltage (Ve) : 1000V
Control voltage limits : 0.85 to 1.1 Vac at 60 Hz
Average consumption at 20 °C (68 °F) and at Vc : 220VA
Mechanical durability of operating cycles : 16,000,000