Siemens 3RV1021-1AA15 Manual Motor Starter/Overload Protector that is adjustable from 1.1-1.6A, mounts on DIN rail and has a Class 10 tripping characteristic. -- Comes preinstalled with 3RV1901-1E front mounted auxiliary contact with 1 NO and 1 NC contact set



Need a slightly lower AMP range? Click here to see the 3RV1021-0KA15.
Need a slightly higher AMP range? Click here to see the 3RV1021-1BA15.

3RV1021-1AA15 Datasheet


Quantity in Stock:(Out of Stock)

Availability : Obsolete - Please see link above for replacement
Product Code: 3RV1021-1AA15
Qty:

Description Detailed Specifications
 
The 3RV1021 MSP’s can be used as Type E self-protected manual combination starters per UL508 (3RV1021 require additional terminal adapers) or as components in Group Installation per NEC 430-53(C) to turn motors on and off. Each device has built-in heater elements that provide overload protection and magnetic trip elements to protect the motor. When the 3RV is used as a component in Group Installation, multiple MSP’s can be installed below one circuit breaker to protect its own motor. A contactor can be mounted to the MSP to provide a remotely operated starter.
Technical Specifications
  • ON/OFF rotary handle with lockout and visible trip indication.
  • Adjustment dial for setting to motor FLA.
  • Class 10 overload trip characteristics.
  • Short circuit trip at 12 times the maximum setting of the FLA adjustment dial.
  • Short circuit current rating:
  • Ambient compensated up to 140° F (applies to side by side mounting).
  • Phase loss sensitivity.
  • Test trip function.